Fire Riser Room Requirements California

Into the fire equipment room.
Fire riser room requirements california. Integrated testing ifc ibc 901 6 2 nfpa 4 is a new standard for testing integrated fire protection and life safety systems. The fire equipment room shall be used for fire protection equipment and controls only. Where a door opens over a landing the landing shall be at least as wide as the door and at least 5 feet long. Riser assembly shall have a minimum of 36 inches of clearance around the pipe.
Fire pump and fire sprinkler riser rooms must be readily accessible at all times but can be locked if a key is available. The temperature in the room must be maintained at 40º fahrenheit or higher to ensure the piping and components do not freeze. The minimum size of the equipment room shall allow adequate firefighter access and mobility with the following minimum clearance requirements. 2018 fire code expands requirements.
In california all sprinkler water must go to sanitary to be treated before going to the ocean. Thereafter the riser goes to floor 1 and above. Fire pump and automatic sprinkler system riser rooms shall be provided with a door s and an unobstructed passageway large enough to allow removal of the largest piece of equipment. Title 24 part 2 section 2 3303 i 1 and i 2 exception.
This could be accom plished using a key box as provided in section 506 1. Permanently installed artificial illumination shall be provided in the automatic sprinkler system. The fire sprinkler riser shall be located on the outside wall between 12 and 18 from that outside wall and at least 12 from any other wall. Fire control rooms shall have a minimum dimension of 5 and not be less than 35 square feet in usable area.
Permanent artificial lighting is now required to be installed by the 2018 ifc ibc. On the first floor there is a floor control valve with drain. Where the door opens into the stairway of a smokeproof enclosure the landing need not have a length of 5 feet. Page 1 of 2.
One side may be a minimum of 18 inches from a wall. Where provided fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary for the installation as defined by the manufacturer with sufficient working room around the stationary equipment.